MACH+ 510 vertical

Mach_verticale_f_5256cdc52eb17
Product Code: VRTP51
Controlled mechanical ventilation systems

The Mach + vertical series is composed of HRV wall-mounted appliances, to ventilate the rooms and to recover the heat that would be expelled with the exhaust air. The high-performance appliances are built with a robust sheet metal structure. They provide the rooms with the necessary air renewal rate, and recover the heat contained in the exhaust air and transfer it to the supply airflow.

Each unit is equipped with:

  • Modulating brushless fans with inverter, for continuous use, energy saving and low noise.
  • Air-to-air polystyrene counterflow heat exchanger, with efficiency greater than 90%.
  • Supply and exhaust filters F7 class.
  • Free cooling, to save cooling energy, manual or automatic according to model.

TAll units, in compliance with European ERP directives and EN standards, are provided with CE marking and related DoP.

Field of use

The units are designed to perform the following functions:

  • Provide renewal air, from outside the building, with flow rate 510 mc / h of fresh air, according to the model.
  • Recover more 90% of the heat from the exhaust air extracted from the rooms to heat (in winter) and cool (in summer) the supply airflow, before it enters the rooms, with considerable energy savings.
  • Filter the air coming from the outside and the air expelled from the wet rooms.

The units are suitable for use in both residential and small commercial buildings.

The air renewal capacity of each unit is of 510 mc/h.

The Mach + vertical series of recuperators are equipped with free-cooling, with manual or automatic activation, according to the models, and signal of clogged filters, in compliance with ERP regulation.

 
TECHNICAL DATA

510_verticale.jpg

 

CODICE - Descrizione Height
(mm)
Base
(mm)

Height without mouthpiece
(mm)

Mouthpiece diameter
(mm)

Depth
(mm)

MACH+ 510 vertical with Manual Freecooling

942 905 905 200 410
MACH+ 510 vertical with Automatic Freecooling 942 905 905 200 410

 

Mode of operation

Fresh air is extracted from the outside, filtered and sent to the premises only after passing, in countercurrent, the high efficiency exchanger with opposite flows. In the exchanger the fresh air receives almost all the heat contained in the exhaust air, which, extracted from the rooms, is sent outside. The free-cooling device excludes the exchanger when, in summer, the outdoor temperature drops below the indoor one.

The air flow can be adjusted according to the requirements, both manually and automatically. Automatic variation is made possible by the installation of sensors capable of detecting odors and pollutants (optional).

 
Features

Description  

MACH+ 360

Vertical

MACH+ 510

vertical
Code   VRFP36-VRTP36 VRFP51 VRTP51
Rated air flow mc/h 394 568
Heat exchange efficiency % > 90 > 90
Heat recovery system in winter W 2660 3732
Heat recovery system in summer W 920 1280
Power consumption W 176 334
Power supply V/ph/Hz 230/1+N/50 230/1+N/50
Net weight kg 75 77
Maximum sound pressure at 1.5 m dB(A) 54 56

 

Note:

The exchange efficiency and the power recovered in winter are for indoor air at +20°C 50% UR and outdoor air -5°C 80% UR

 
Specification text

Cod.VRTS36 - Mach+ 510 vertical with manual free-cooling

Ductable heat recovery unit in galvanized sheet for ceiling mount, with function of air renewal and heat recovery from exhausted air for maximum energy efficiency. Renewal air flow rate 510 m3 / h, exchanger efficiency in counter current greater than 90%, sound power 54 dB (A) according to UNI EN ISO 3746:1997. Manual built-in Free-cooling and clogged filters signal according to ErP 2018.

Cod. VRFS36 - horizontal Mach+ 510 vertical with automatic free-cooling

Ductable heat recovery unit in galvanized sheet for ceiling mount, with function of air renewal and heat recovery from exhausted air for maximum energy efficiency. Renewal air flow rate 510 m3 / h, exchanger efficiency in counter current greater than 90%, sound power 54 dB (A) according to UNI EN ISO 3746:1997. Built-in automatic free-cooling and clogged filters signal according to ErP 2018

 
Diagrams / charts

Prevalence diagrams

510pre.jpg

Recovery efficiency diagrams

510veertisadka.jpg

 
Download

Documenti da scaricare

 

 

 
 


Related products