Newsletter Subscription
Enter your email and we will send you more information
The KERS+ series consists of devices for mechanical ventilation with dual flow, featuring heat recovery, to be installed in a dedicated wall opening. The high-performance devices are designed to provide the necessary air renewal rate to individual spaces, recovering heat from the exhaust air and transferring it to the incoming air in the environment.
For the installation of grilles on inaccessible external walls, specific flexible grilles for Kers are available (optional). They are installed from inside the room without the need for scaffolding or external platforms. The grilles, provided as an accessory for both Kers+ 25 and Kers+ 50, are available in white finish or in the traditional copper-effect finish to maintain the aesthetics of the building.
The grids for Kers+ 25 are as follows:
CODE | DESCRIPTION |
VTGF01 | FLEXIBLE EXTERNAL GRILLE FOR KERS+ 25 WHITE |
VTGF02 | FLEXIBLE EXTERNAL GRILLE FOR KERS+ 25 COPPER-COLORED |
for Kers+ 50 are :
CODE | DESCRIPTION |
VTGF03 | FLEXIBLE EXTERNAL GRILLE FOR KERS+ 50 WHITE |
VTGF04 |
Description | Recovery unit KERS+ 25 with remote control | Recovery unit KERS+ 50 with remote control | Recovery unit KERS+ 60 with remote control | Recovery unit KERS+ 100 with remote control | |
Codes | VRKS27W | VRKS52W | VRKS60W | VRKS00W | |
Airflow at maximum speed | mc/h | 25 | 50 | 60 | 100 |
Air exchange rate | mc/h | 12,5 | 25 | 30 | 50 |
Efficiency of the ceramic heat exchanger | % | Up to 97% | Up to 97% | Up to 94% | Up to 94% |
Temperature of the treated air | °C | -20 / +40 | -20 / +40 | -20 / +40 | -20 / +40 |
Electric power absorbed at max speed | W | 3.35 | 4,3 | 4,8 | 10,5 |
Electric current absorbed at max speed | A | 0.016 | 0,020 | 0,022 | 0,05 |
Onboard filters | - | 2 | 2 | 2 | 2 |
Filtration class EN 779 | G3 | G3 | G3 | G3 | |
Power supply | V/ph/ Hz |
110V-240V / 1 / 50-60Hz | |||
Wall hole diameter | mm | 102 | 162 | 162 | 202 |
Minimum wall thickness | mm | 280 | 280 | 280 | 280 |
Protection | - | IPX4 | IPX4 | IPX4 | IPX4 |
Description | u.m. | KERS+ 25 (VRKS27W) | KERS+ 50 (VRKS52W) | KERS+ 60 (VRKS60W) | KERS+ 100 (VRKS00W) |
Maximum Speed | |||||
Air flowrate | m³/h | 25 | 50 | 60 | 100 |
Effective exchange rate | m³/h | 12,5 | 25 | 30 | 50 |
Sound pressure at 3 m | dB(A) | 28.5 | 25,8 | 26.4 | 29,2 |
Medium Speed | |||||
Air flowrate | m³/h | 17,5 | 35 | 42 | 70 |
Effective exchange rate | m³/h | 8.7 | 17,5 | 21 | 35 |
Sound pressure at 3 m | dB(A) | 19 | 16.5 | 16.5 | 20 |
Minimum Speed | |||||
Air flowrate | m³/h | 9 | 19 | 22 | 50 |
Effective exchange rate | m³/h | 4.5 | 9.5 | 11 | 25 |
Sound pressure at 3 m | dB(A) | 7.8 | 7.6 | 7.6 | 15 |
Super Minimum Speed | |||||
Air flowrate | m³/h | 7 | 12 | 16 | 40 |
Effective exchange rate | m³/h | 3.5 | 6 | 8 | 20 |
Sound pressure at 3 m | dB(A) | 4 | 4 | 5 | 11 |
Acoustic Attenuation | |||||
Outside noise attenuation (fan off) | dB(A) | 44 | 42 | 42 | 40 |
Specification | Unit | VRKS27W - KERS+ 25 | VRKS52W - KERS+ 50 | VRKS60W - KERS+ 60 | VRKS00W - KERS+ 100 |
Brand | - | Ideal Clima | Ideal Clima | Ideal Clima | Ideal Clima |
Specific Energy Consumption (SEC), kWh/(m²·a) | |||||
Cold | - | -82.7 | -85.1 | -84.3 | -84.9 |
Tempered | - | -40.8 | -42.2 | -41.8 | -41.4 |
Hot | - | -16.8 (A) | -16.6 (A) | -17.5 (A) | -16.5 (A) |
Type of ventilation unit | - | Bidirectional | Bidirectional | Bidirectional | Bidirectional |
Installed drive type | - | Multiple Speeds | Multiple Speeds | Multiple Speeds | Multiple Speeds |
Type of heat recovery | - | Regeneration | Regeneration | Regeneration | Regeneration |
Efficiency at 13°C | % | 75% | 80% | 78% | 83% |
Max flow rate | m³/h | 25 | 50 | 60 | 100 |
Power consumption | W | 3.35 | 4.3 | 5 | 10.5 |
Sound power level (Lw) | dB(A) | 42 | 40 | 42 | 44 |
Reference flow rate | m³/s | 0.0047 | 0.0097 | 0.0117 | 0.0195 |
Reference pressure | Pa | 0 | 0 | 0 | 0 |
Specific power input (SPI) | W/(m³/h) | 0.15 | 0.13 | 0.13 | 0.15 |
Type of control | - | Local Environment Control | Local Environment Control | Local Environment Control | Local Environment Control |
Max internal leakage | % | 1.5% | 1.5% | 1.5% | 1.5% |
Max external leakage | % | 0% | 0% | 0% | 0% |
Mixing rate | % | 1% | 1% | 1% | 1% |
Airflow sensitivity variation | m³/h | 0.41 | 0.55 | 0.55 | 0.55 |
Indoor/outdoor airtightness | m³/h | 0.49 | 0.6 | 0.6 | 0.6 |
Internet address | - | www.idealclima.eu | |||
Annual electricity consumption (AEC) | kWh/100m²·a | 1.22 | 1.06 | 1.06 | 0.15 |
Annual Heating Saved (AHS), kWh primary energy/m²·a | |||||
Cold | - | 85.7 | 87.8 | 87.8 | 86.1 |
Tempered | - | 43.8 | 44.9 | 44.4 | 44.4 |
Hot | - | 19.8 | 20 | 19.9 | 19.9 |