Newsletter Subscription
Enter your email and we will send you more information
Single-room heat recovery unit for decentralized mechanical ventilation with A+ energy class
KERS Premium is the ideal solution for those seeking high performance and maximum comfort in decentralized mechanical ventilation. This high-efficiency single-room heat recovery unit is designed to provide fresh air renewal, recover heat from exhaust air and transfer it to the incoming air, improving indoor comfort and energy efficiency.
Its key distinguishing feature is the stainless steel rectangular-cell heat exchanger, delivering efficiency up to 97% depending on the size, together with high durability, hygiene and long-term performance. Kers Premium also includes a negative ion ionizer, automatic wind damper, transparent display with touch keys, twilight sensor, humidity sensor and Wi-Fi Ready setup.
![]()

Kers Premium has been developed for users looking for a higher level of construction quality and performance in decentralized heat recovery ventilation. The stainless steel heat exchanger is the technological core of the product: more compact, more efficient and more durable over time, it enhances indoor comfort and energy recovery in residential applications and renovation projects.
KERS Premium units are designed to perform the following functions in each single room:
The units are intended for residential and light commercial applications, especially where centralized ventilation systems are not considered necessary. They can be installed through perimeter walls and are therefore particularly suitable for refurbishment and partial renovation of rooms affected by mould caused by insufficient ventilation.
Since they work in alternating mode, 50% of the time in extraction and 50% in supply, the effective renewal airflow is approximately half of the nominal maximum airflow.

The unit is equipped with a low-consumption EC motor fan, able to reverse the airflow inside the heat exchanger, and operates in two phases:
The fan extracts warm air from the room and pushes it outside through the heat exchanger. During this phase, the stainless steel exchanger stores the heat contained in the exhaust air.
The fan reverses the airflow and draws cold air from outside. In contact with the heat exchanger, the incoming air is pre-heated before entering the room.

The standard remote control allows you to:
For installation on inaccessible external walls, special flexible grilles for Kers (optional) are available. They can be installed completely from inside the room, without the need for scaffolding or external lifting platforms. The grilles, supplied as accessories for Kers Premium, are available in white finish or in the traditional copper-effect finish, so as not to alter the aesthetics of the building.
The grilles for Kers Premium 25 are the following:
| Code | Description |
|---|---|
| VTGF01 | FLEXIBLE EXTERNAL GRILLE DN 100 WHITE |
| VTGF02 | FLEXIBLE EXTERNAL GRILLE DN 100 COPPER |
The grilles for Kers Premium 60 are the following:
| Code | Description |
|---|---|
| VTGF03 | FLEXIBLE EXTERNAL GRILLE DN 160 WHITE |
| VTGF04 | FLEXIBLE EXTERNAL GRILLE DN 160 COPPER |
The grilles for Kers Premium 100 are the following:
| Code | Description |
|---|---|
| VTGF05 | FLEXIBLE EXTERNAL GRILLE DN 200 WHITE |
| VTGF06 | FLEXIBLE EXTERNAL GRILLE DN 200 COPPER |



| Description | Unit | KERS Premium 25 | KERS Premium 60 | KERS Premium 100 |
|---|---|---|---|---|
| Code | - | VRKP27W | VRKP60W | VRKP00W |
| Air flowrate at max speed | mc/h | 25 | 60 | 100 |
| Air renewal | mc/h | 12.5 | 30 | 50 |
| Heat recovery efficiency up to | % | 97% | 97% | 94% |
| Treated air temperature | °C | -20 / +40 | -20 / +40 | -20 / +40 |
| Electrical power input at max speed | W | 3.35 | 4.8 | 10.5 |
| Current input at max speed | A | 0.016 | 0.022 | 0.05 |
| Built-in filters | - | 2 | 2 | 2 |
| Filtration class EN 779 | - | G3 | G3 | G3 |
| Power supply | V/ph/Hz | 110V-240V/1/50-60Hz | ||
| Wall hole diameter (2° outward slope) | mm | 102 | 162 | 202 |
| Minimum wall thickness | mm | 280 | 280 | 280 |
| Protection | - | IP X4 | IP X4 | IP X4 |
| Speed | Parameter | Unit | KERS Premium 25 | KERS Premium 60 | KERS Premium 100 |
|---|---|---|---|---|---|
| Maximum | Air flowrate | m3/h | 25 | 60 | 100 |
| Effective renewal airflow | m3/h | 12.5 | 30 | 50 | |
| Sound pressure at 3 m | dB(A) | 28.5 | 26.4 | 28.4 | |
| Medium | Air flowrate | m3/h | 17.5 | 42 | 70 |
| Effective renewal airflow | m3/h | 8.7 | 21 | 35 | |
| Sound pressure at 3 m | dB(A) | 19 | 16.5 | 20 | |
| Minimum | Air flowrate | m3/h | 9 | 22 | 50 |
| Effective renewal airflow | m3/h | 4.5 | 11 | 25 | |
| Sound pressure at 3 m | dB(A) | 7.8 | 7.6 | 15 | |
| Super minimum | Air flowrate | m3/h | 7 | 16 | 40 |
| Effective renewal airflow | m3/h | 3.5 | 8 | 20 | |
| Sound pressure at 3 m | dB(A) | 4 | 5 | 5 | |
| Sound insulation from outside noise with fan off | dB(A) | 44 | 42 | 40 | |