NUVI is the fan coil designed for concealed false-ceiling installation, ideal for residential comfort. Thanks to its height of only 25 cm and its high-efficiency heat exchanger coil, it ensures excellent performance in heating, cooling and dehumidification, even in modern heat pump systems.
The unit body in EPP (expanded polypropylene) ensures excellent thermal and acoustic insulation, very low weight and high mechanical strength. The hybrid mixed-flow fans, managed through a 0-10 V signal, allow precise speed modulation and high airflows even in ducted systems, while maintaining higher available static pressure than traditional centrifugal fans. The air filter can be removed from the return side, the condensate tray has a DN 16 drain and the 3/4” F water connections are positioned on the left-hand side.

NUVI is designed to be installed inside false ceilings in residential environments, with a compact yet high-performance structure. The range has been developed to create simple ducted layouts and distribute air to multiple rooms, with air return from the rear side ducted for a single room or drawn through a single grille positioned below the unit.

The technological core of NUVI is the mixed-flow fan, which combines the high airflow typical of axial fans with the pressure capability of centrifugal fans. This provides an optimal balance between compact size, available static pressure and low noise, with high performance even in systems with airflow resistance.
| Mixed flow | Modulating motor |
|---|---|
The EPP structure makes NUVI light, durable and easy to install. This material offers high thermal and mechanical resistance, absorbs shocks and vibrations, improves acoustic comfort and helps reduce condensation, heat loss and corrosion. Its very low weight also simplifies transport and installation.

The DC inverter motors are managed through a 0-10 V signal to achieve the best possible speed modulation. Continuous control allows operation at low speeds, reducing noise, consumption and comfort fluctuations compared with traditional on/off systems. NUVI can be integrated with Integra Control Zone + Integra Point TH, Integra Touchscreen, Vision+ or with MultiEasy modulating plenum systems.

| NUVI 320 | NUVI 510 | NUVI 850 | NUVI 1360 |
|---|---|---|---|
| Nominal airflow 320 m³/h | Nominal airflow 510 m³/h | Nominal airflow 850 m³/h | Nominal airflow 1360 m³/h |
| Code TCU03D | Code TCU05D | Code TCU08D | Code TCU14D |
NUVI fan coils are designed to:
Nuvi’s filter uses a modular system with easy extraction, designed to allow quick maintenance even where inspection hatches are small. The modular structure of the unit also allows servicing without dismantling the entire appliance.

Continuous 0÷100% modulation of heating output helps maintain more stable comfort, with lower temperature fluctuations and reduced consumption. The highly quiet hybrid fans make it possible to achieve the required airflow even with higher available static pressure than traditional centrifugal fans.

NUVI is equipped with a 230 V valve control output for normally closed actuators, a condensate collection tray with a removable external section to further reduce overall dimensions, and extremely low weight to simplify transport and installation. Thanks to its innovative features, NUVI is a patent-protected product.

| CODE | DESCRIPTION | A [mm] | B [mm] | C [mm] |
|---|---|---|---|---|
| TCU03D | NUVI 320 | 622 | 512 | 418 |
| TCU05D | NUVI 510 | 902 | 792 | 698 |
| TCU08D | NUVI 850 | 1182 | 1072 | 978 |
| TCU14D | NUVI 1360 | 1462 | 1352 | 1258 |
| Description | NUVI 320 | NUVI 510 | NUVI 850 | NUVI 1360 | |
|---|---|---|---|---|---|
| Product code | TCU03D | TCU05D | TCU08D | TCU14D | |
| Total cooling capacity 7°C (1) | kW | 1.95 | 2.79 | 4.46 | 7.25 |
| Sensible cooling capacity | kW | 1.41 | 2.02 | 3.22 | 5.25 |
| Water flow rate | l/min | 5.6 | 8.0 | 12.0 | 20.0 |
| Pressure drop unit only | kPa | 0 | 36 | 32 | 46 |
| Pressure drop 2- and 3-way valve KVs=4 | kPa | 0.7 | 1.4 | 3.2 | 9.1 |
| Heating capacity 45°C (2) | kW | 2.19 | 3.36 | 5.38 | 8.73 |
| Water flow rate | l/min | 6.3 | 10.0 | 15.0 | 25.0 |
| Pressure drop unit only | kPa | 18 | 58 | 51 | 72 |
| Pressure drop 2- and 3-way valve KVs=4 | kPa | 1.0 | 2.2 | 5.0 | 14.0 |
| Airflow at 30 Pa | m³/h | 320 | 510 | 850 | 1360 |
| Nominal air pressure | Pa | 30 | 30 | 30 | 30 |
| Sound pressure max speed (*) | dB (A) | 36 | 42 | 46 | 48 |
| Power supply – protection rating | V/ph/Hz | 230/1+N/50 ---- IP23 | |||
| Max electrical input | W | 20 | 35 | 50 | 65 |
| Hydraulic connections | Inches | Rc 3/4” (DN20) | |||
| Condensate drain pipe | mm | DN 16 | |||
| Maximum working pressure | MPa | 1.6 | |||
| Net weight | kg | 8.5 | 11.2 | 13.9 | 16.6 |
(1) Inlet water temp. 7°, Δ T 5 °C, room temp. 27 °C RH 47% (UNI EN 1397:2015)
(2) Inlet water temp. 45°, Δ T 5 °C, room temp. 20 °C (UNI EN 1397:2015)
(*) Sound pressure (dBA) r=1.5 m, Q=1 (UNI EN ISO 3741:2010)